VendorsSchneider Electricmodicon_m251_firmwareany version
Vulnerabilities

Schneider Electric Modicon M251 Firmware any version

Ranked by severity, then by exploit likelihood. Click a CVE ID for its full record.

10CVEs
CVE-2017-6028
An Insufficiently Protected Credentials issue was discovered in Schneider Electric Modicon PLCs Modicon M241, all firmware versions, and Modicon M251, all firmware versions. Log-in credentials are sent over the network with Base64 encoding leaving them susceptible to sniffing. Sniffed credentials could then be used to log into the web application.
Published 2017-06-30 · Modified
9.8EPSS 0.023
CVE-2020-7487
A CWE-345: Insufficient Verification of Data Authenticity vulnerability exists which could allow the attacker to execute malicious code on the Modicon M218, M241, M251, and M258 controllers.
Published 2020-04-22 · Modified
9.8EPSS 0.007
CVE-2017-6026
A Use of Insufficiently Random Values issue was discovered in Schneider Electric Modicon PLCs Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The session numbers generated by the web application are lacking randomization and are shared between several users. This may allow a current session to be compromised.
Published 2017-06-30 · Modified
9.11 PoCEPSS 0.318
CVE-2019-6820
A CWE-306: Missing Authentication for Critical Function vulnerability exists which could cause a modification of device IP configuration (IP address, network mask and gateway IP address) when a specific Ethernet frame is received in all versions of: Modicon M100, Modicon M200, Modicon M221, ATV IMC drive controller, Modicon M241, Modicon M251, Modicon M258, Modicon LMC058, Modicon LMC078, PacDrive Eco ,PacDrive Pro, PacDrive Pro2
Published 2019-05-22 · Modified
8.2EPSS 0.013
CVE-2021-22699
Improper Input Validation vulnerability exists in Modicon M241/M251 logic controllers firmware prior to V5.1.9.1 that could cause denial of service when specific crafted requests are sent to the controller over HTTP.
Published 2021-05-26 · Modified
7.8EPSS 0.010
CVE-2020-7488
A CWE-319: Cleartext Transmission of Sensitive Information vulnerability exists which could leak sensitive information transmitted between the software and the Modicon M218, M241, M251, and M258 controllers.
Published 2020-04-22 · Modified
7.5EPSS 0.009
CVE-2025-13901
CWE-404 Improper Resource Shutdown or Release vulnerability exists that could cause partial Denial of Service on Machine Expert protocol when an unauthenticated attacker sends malicious payload to occupy active communication channels.
Published 2026-03-10 · Analyzed
6.9EPSS 0.005
CVE-2017-6030
Schneider Electric Modicon PLCs Predictable Value Range from Previous Values
Published 2017-06-30 · Modified
6.5EPSS 0.021
CVE-2024-6528
CWE-79: Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists that could cause a vulnerability leading to a cross-site scripting condition where attackers can have a victim’s browser run arbitrary JavaScript when they visit a page containing the injected payload.
Published 2024-07-11 · Modified
6.1EPSS 0.003
CVE-2025-13902
CWE-79 Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists that could cause condition where authenticated attackers can have a victim’s browser run arbitrary JavaScript when the victim hovers over a maliciously crafted element on a web server containing the injected payload.
Published 2026-03-10 · Analyzed
5.4EPSS 0.002