VendorsSchneider Electrictriconex_tricon_mp_3008_firmwareall versions
Vulnerabilities

Schneider Electric Schneider-Electric Triconex Tricon MP 3008 Firmware

Ranked by severity, then by exploit likelihood. Click a CVE ID for its full record.

2CVEs
CVE-2018-8872
In Schneider Electric Triconex Tricon MP model 3008 firmware versions 10.0-10.4, system calls read directly from memory addresses within the control program area without any verification. Manipulating this data could allow attacker data to be copied anywhere within memory.
Published 2018-05-04 · Modified
9.3EPSS 0.022
CVE-2018-7522
In Schneider Electric Triconex Tricon MP model 3008 firmware versions 10.0-10.4, when a system call is made, registers are stored to a fixed memory location. Modifying the data in this location could allow attackers to gain supervisor-level access and control system states.
Published 2018-05-04 · Modified
7.2EPSS 0.004