VendorsSchneider Electrictristation_1131any version
Vulnerabilities

Schneider Electric Tristation 1131 any version

Ranked by severity, then by exploit likelihood. Click a CVE ID for its full record.

4CVEs
CVE-2020-7485
**VERSION NOT SUPPORTED WHEN ASSIGNED** A legacy support account in the TriStation software version v4.9.0 and earlier could cause improper access to the TriStation host machine. This was addressed in TriStation version v4.9.1 and v4.10.1 released on May 30, 2013.1
Published 2020-04-15 · Modified
9.8EPSS 0.019
CVE-2020-7484
**VERSION NOT SUPPORTED WHEN ASSIGNED** A vulnerability with the former 'password' feature could allow a denial of service attack if the user is not following documented guidelines pertaining to dedicated TriStation connection and key-switch protection. This vulnerability was discovered and remediated in versions v4.9.1 and v4.10.1 on May 30, 2013. This feature is not present in version v4.9.1 and v4.10.1 through current. Therefore, the vulnerability is not present in these versions.
Published 2020-04-15 · Modified
7.5EPSS 0.013
CVE-2020-7491
**VERSION NOT SUPPORTED WHEN ASSIGNED** A legacy debug port account in TCMs installed in Tricon system versions 10.2.0 through 10.5.3 is visible on the network and could allow inappropriate access. This vulnerability was remediated in TCM version 10.5.4.
Published 2020-07-23 · Modified
7.5EPSS 0.013
CVE-2020-7483
**VERSION NOT SUPPORTED WHEN ASSIGNED** A vulnerability could cause certain data to be visible on the network when the 'password' feature is enabled. This vulnerability was discovered in and remediated in versions v4.9.1 and v4.10.1 on May 30, 2013. The 'password' feature is an additional optional check performed by TS1131 that it is connected to a specific controller. This data is sent as clear text and is visible on the network. This feature is not present in TriStation 1131 versions v4.9.1 and v4.10.1 through current. Therefore, the vulnerability is not present in these versions.
Published 2020-04-15 · Modified
7.5EPSS 0.009