VendorsSiemenscp-8050all versions
Vulnerabilities

Siemens CP-8050 -

Ranked by severity, then by exploit likelihood. Click a CVE ID for its full record.

3CVEs
CVE-2023-28489
A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05), CP-8050 MASTER MODULE (All versions < CPCI85 V05). Affected devices are vulnerable to command injection via the web server port 443/tcp, if the parameter “Remote Operation” is enabled. The parameter is disabled by default. The vulnerability could allow an unauthenticated remote attacker to perform arbitrary code execution on the device.
Published 2023-04-11 · Modified
9.8EPSS 0.028
CVE-2023-36380
A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05.11 (only with activated debug support)), CP-8050 MASTER MODULE (All versions < CPCI85 V05.11 (only with activated debug support)). The affected devices contain a hard-coded ID in the SSH `authorized_keys` configuration file. An attacker with knowledge of the corresponding private key could login to the device via SSH. Only devices with activated debug support are affected.
Published 2023-10-10 · Modified
9.8EPSS 0.004
CVE-2023-42796
A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05.11), CP-8050 MASTER MODULE (All versions < CPCI85 V05.11). The web server of affected devices fails to properly sanitize user input for the /sicweb-ajax/tmproot/ endpoint. This could allow an authenticated remote attacker to traverse directories on the system and download arbitrary files. By exploring active session IDs, the vulnerability could potentially be leveraged to escalate privileges to the administrator role.
Published 2023-10-10 · Modified
8.8EPSS 0.007