VendorsSiemenswincc_tia_portal11.0
Vulnerabilities

Siemens WinCC (TIA Portal) 11.0

Ranked by severity, then by exploit likelihood. Click a CVE ID for its full record.

7CVEs
CVE-2011-4515
Siemens WinCC (TIA Portal) 11 uses a reversible algorithm for storing HMI web-application passwords in world-readable and world-writable files, which allows local users to obtain sensitive information by leveraging (1) physical access or (2) Sm@rt Server access.
Published 2013-03-21 · Modified
4.6EPSS 0.004
CVE-2013-0670
CRLF injection vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote attackers to inject arbitrary HTTP headers and conduct HTTP response splitting attacks via a crafted URL.
Published 2013-03-21 · Modified
4.3EPSS 0.015
CVE-2013-0667
Cross-site scripting (XSS) vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote attackers to inject arbitrary web script or HTML via a crafted URL.
Published 2013-03-21 · Modified
4.3EPSS 0.015
CVE-2013-0668
Multiple cross-site scripting (XSS) vulnerabilities in the HMI web application in Siemens WinCC (TIA Portal) 11 allow remote attackers to inject arbitrary web script or HTML via a crafted URL.
Published 2013-03-21 · Modified
4.3EPSS 0.015
CVE-2013-0671
Directory traversal vulnerability in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to read HMI web-application source code and user-defined scripts via a crafted URL.
Published 2013-03-21 · Modified
4.0EPSS 0.023
CVE-2013-0669
The HMI web application in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to cause a denial of service (daemon crash) via a crafted HTTP request.
Published 2013-03-21 · Modified
4.0EPSS 0.018
CVE-2013-0672
Cross-site scripting (XSS) vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to inject arbitrary web script or HTML via unspecified data.
Published 2013-03-21 · Modified
3.5EPSS 0.012