VendorsHoneywellsaia_pg5_controls_suiteall versions
Vulnerabilities

Honeywell (Saia Burgess Controls) Saia PG5 Controls Suite

Ranked by severity, then by exploit likelihood. Click a CVE ID for its full record.

9CVEs
CVE-2023-51599
Honeywell Saia PG5 Controls Suite Directory Traversal Remote Code Execution Vulnerability
Published 2024-05-03 · Analyzed
8.8EPSS 0.016
CVE-2023-51603
Honeywell Saia PG5 Controls Suite CAB File Parsing Directory Traversal Remote Code Execution Vulnerability
Published 2024-05-03 · Analyzed
8.8EPSS 0.016
CVE-2022-30319
Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.
Published 2022-07-28 · Modified
8.1EPSS 0.007
CVE-2023-51600
Honeywell Saia PG5 Controls Suite XML External Entity Processing Information Disclosure Vulnerability
Published 2024-05-03 · Analyzed
6.5EPSS 0.008
CVE-2023-51601
Honeywell Saia PG5 Controls Suite XML External Entity Processing Information Disclosure Vulnerability
Published 2024-05-03 · Analyzed
6.5EPSS 0.008
CVE-2023-51602
Honeywell Saia PG5 Controls Suite XML External Entity Processing Information Disclosure Vulnerability
Published 2024-05-03 · Analyzed
6.5EPSS 0.008
CVE-2023-51604
Honeywell Saia PG5 Controls Suite XML External Entity Processing Information Disclosure Vulnerability
Published 2024-05-03 · Analyzed
6.5EPSS 0.008
CVE-2023-51605
Honeywell Saia PG5 Controls Suite XML External Entity Processing Information Disclosure Vulnerability
Published 2024-05-03 · Analyzed
6.5EPSS 0.008
CVE-2022-30320
Saia Burgess Controls (SBC) PCD through 2022-05-06 uses a Broken or Risky Cryptographic Algorithm. According to FSCT-2022-0063, there is a Saia Burgess Controls (SBC) PCD S-Bus weak credential hashing scheme issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication is done by using the S-Bus 'write byte' message to a specific address and supplying a hashed version of the password. The hashing algorithm used is based on CRC-16 and as such not cryptographically secure. An insecure hashing algorithm is used. An attacker capable of passively observing traffic can intercept the hashed credentials and trivially find collisions allowing for authentication without having to bruteforce a keyspace defined by the actual strength of the password. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.
Published 2022-07-28 · Modified
4.3EPSS 0.003